Product Brochure
Download :
KEB Electric Steam Boiler.pdf 577.21 KBElectrical Boiler
![]() |
KEB SERIES: ELECTRIC STEAM BOILER
|
|
HIGH EFFICIENCY ELECTRIC BOILER FEATURES AND ADVANTAGES KAWAN® vertical design boiler is built to ASME code and standard. As the heating elements are totally immersed in water and pressure vessel is fully insulated, they are very efficient. Radiation losses are minimal. Electric boilers have no wasted fuel and are environmentally friendly. KAWAN uses low watt density stainless steel element which will not melt or anneal as easily.
|
|
TECHNICAL SPECIFICATIONS
|
Model, KEB |
010 |
020 |
030 |
040 |
050 |
075 |
100 |
150 |
200 |
250 |
|
Unit Size, kW |
10 |
20 |
30 |
40 |
50 |
75 |
100 |
150 |
200 |
250 |
|
Steam Output, kg/hr * |
15 |
31 |
46 |
61 |
77 |
115 |
153 |
230 |
306 |
383 |
|
Boiler Height, mm |
940 |
940 |
940 |
940 |
1800 |
1800 |
1930 |
1930 |
1930 |
1930 |
|
Boiler Width, mm |
910 |
910 |
910 |
910 |
910 |
910 |
960 |
960 |
960 |
1190 |
|
Boiler Depth, mm |
915 |
915 |
915 |
915 |
860 |
860 |
910 |
910 |
910 |
1140 |
|
Water Capacity, L |
24.82 |
24.82 |
24.82 |
24.82 |
144.97 |
112.24 |
184.52 |
184.52 |
184.52 |
424.56 |
|
Steam Outlet connection, mm |
20 |
20 |
20 |
20 |
25 |
25 |
40 |
40 |
40 |
80 |
|
Feed Water Inlet Connection, mm |
20 |
20 |
20 |
20 |
20 |
20 |
25 |
25 |
25 |
25 |
|
Blow Down Outlet Connection, mm |
25 |
25 |
25 |
25 |
25 |
25 |
32 |
32 |
32 |
40 |
|
Model, KEB |
300 |
500 |
750 |
1000 |
1250 |
1500 |
1750 |
2000 |
2500 |
3000 |
|
Unit Size, kW |
300 |
500 |
750 |
1000 |
1250 |
1500 |
1750 |
2000 |
2500 |
3000 |
|
Steam Output, kg/hr * |
459 |
765 |
1148 |
1530 |
1913 |
2295 |
2678 |
3060 |
3825 |
4590 |
|
Boiler Height, mm |
1930 |
1930 |
2030 |
2030 |
2030 |
2030 |
2030 |
2030 |
2030 |
2030 |
|
Boiler Width, mm |
1190 |
1190 |
1570 |
1570 |
2070 |
2070 |
2070 |
2070 |
2500 |
2500 |
|
Boiler Depth, mm |
1140 |
1140 |
1600 |
1600 |
2150 |
2150 |
2150 |
2150 |
2650 |
2650 |
|
Water Capacity, L |
424.56 |
424.56 |
1407.61 |
1407.61 |
3067.37 |
3067.37 |
3067.37 |
3067.37 |
4854.8 |
4854.8 |
|
Steam Outlet connection, mm |
80 |
80 |
80 |
80 |
100 |
100 |
100 |
100 |
150 |
150 |
|
Feed Water Inlet Connection, mm |
25 |
25 |
32 |
32 |
32 |
32 |
32 |
32 |
50 |
50 |
|
Blow Down Outlet Connection, mm |
40 |
40 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
*Feed water temperature at 82°
The information above manufacturing change without notice